Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 634 60 178 247 306 306 0 226 440 109 79 307 0 0 0 0 799 47 689 0 202 33,756 488,895 404,032 -36,895
mg1 675 243 453 574 861 713 0 526 800 568 0 0 74 148 0 0 1,968 46 1,754 0 3,093 82,549 1,888,927 1,457,068 -249,638
mg2 684 365 645 780 1,033 909 81 605 0 1,759 20 100 104 64 0 0 2,569 41 2,658 5 3,895 114,449 3,784,006 2,495,568 330,404
mg3 646 25 139 215 385 385 0 306 0 579 40 10 6 77 0 0 930 63 430 30 4,378 33,010 1,520,316 1,091,779 -32,663
Summary None 757 1,414 1,816 2,541 2,313 81 1,663 1,240 3,015 139 417 184 289 0 0 6,266 46 5,531 6 202 263,764 7,682,144 5,448,447 11,208

Report Generated

2024-02-23 17:16:18.644388

User Warnings

Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.
Pre-existing battery battery_684_existing will not be utilized to support loads in microgrid mg2.
Pre-existing battery battery_646_existing will not be utilized to support loads in microgrid mg3.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Cost Estimate ($)
mg0 mg0 Microgrid Design 100,000
mg0 mg0 Microgrid Controls 100,000
mg0 632633 SCADA disconnect switch 50,000
mg0 634a_data_center AMI disconnect meter 300
mg0 634b_radar AMI disconnect meter 300
mg0 634c_atc_tower AMI disconnect meter 300
mg1 mg1 Microgrid Design 100,000
mg1 mg1 Microgrid Controls 100,000
mg1 671692 SCADA disconnect switch 50,000
mg1 675a_hospital 3-phase relay 20,000
mg1 675b_residential1 3-phase relay 20,000
mg1 675c_residential1 3-phase relay 20,000
mg1 692_warehouse2 3-phase relay 20,000
mg2 mg2 Microgrid Design 100,000
mg2 mg2 Microgrid Controls 100,000
mg2 671684 SCADA disconnect switch 50,000
mg2 684_command_center AMI disconnect meter 300
mg2 652_residential AMI disconnect meter 300
mg2 611_runway AMI disconnect meter 300
mg3 mg3 Microgrid Design 100,000
mg3 mg3 Microgrid Controls 100,000
mg3 632645 SCADA disconnect switch 50,000
mg3 645_hangar AMI disconnect meter 300
mg3 646_office AMI disconnect meter 300

Description